Home
 

M66 R&L Specifications

MODEL M66 R & L Media Air Cleaner

media air cleaner

The M66 is a self-contained media air cleaning system designed for general background or ducted for source capture applications. The M66 can be ordered with three-stage filtration which will effectively remove a broad range of airborne contaminants including fine dusts, smoke, soot, vapors, mist, VOC's and more at a rate of up to 3200 cfm.

M66 R&L FEATURES & SPECIFICATIONS

DIMENSIONS:
27 1/8"H x 26 1/2"W x 56"L

WEIGHT:
250 lbs. installed
297 lbs. shipping weight

CABINET:
16-gauge welded steel cabinet with baked enamel textured coated finish.

POWER INPUT:

Voltage Phase 1 HP Amps 2 HP Amps 3 HP Amps
110-120 1 12 NA NA
208-240 1 6.6 9 NA
208-240 3 3.8 7 9
440-480 3 1.9 3.5 4.4
 
PRIMARY FILTER:
24 x 24 x 22, 8 pocket, 66 sq. ft. of synthetic media.
Optional filters can increase filter media to 200 sq. ft.

AIRFLOW/EFFICIENCY:

Stock No. Filter CFM=Cubic Feet Per Minute Per Arm
1 HP 2 HP 3 HP
41072 95% Bag 1940 CFM 2620 CFM 3020CFM
41056 85% Bag 2030 CFM 2675 CFM 3150 CFM
41055 65% Bag 2150 CFM 2800 CFM 3170 CFM
41057 50% Bag 2190 CFM 2830 CFM 3200 CFM
41061 35% Bag 2210 CFM 2850 CFM 3225 CFM
 

AMBIENT TEMP:
175° Maximum

MOUNTING:
Standing or hanging cabinet with horizontal airflow. Ceiling mount brackets – standard.

PREFILTER:
30-35% efficient pleated filters, 24 x 24 x 4. Filter media is a cotton and synthetic blend. Total prefilter media area is 29.5 ft.

MOTOR:
1 HP sealed ball bearings and thermally protected. Adjustable motor sheave allows for field adjustments to the rated airflow.

BLOWER:
Forward curved, ball bearing, belt driven centrifugal blower. This blower is capable of moving 4400 cfm free air.

INSTRUMENTATION:
Dirty Filter Gage – Factory installed pressure gage designed to determine filter replacement cycle.
Indicator Light – Light indicates that the blower motor is energized properly.

FILTER ACCESS:
Side load track system with hinged access door.

SOUND LEVELS:
70 dBA at 15 ft., 73 dBA at 9 ft.

M66L media air cleaner

STANDARD FEATURES:

  • 36-month parts warranty
  • 1 HP maintenance-free motor
  • Dirty filter gauge
  • 10 ft. power cord with molded plug
  • Completely prewired including 3 phase

OPTIONAL ACCESSORIES:

  • 2, 3 and 5 HP BI blower packages
  • Silencer
  • Extended service filters
  • HEPA and electrostatic add-on modules
  • Wrap around prefilter
  • Minihelic® filter gauge
  • Source capture plenums
  • 45 or 90 lbs of activated carbon
  • Impinger assembly
  • Oil mist bag filter
  • 65% pre filter

 

Click here for printable version of M66 R & L Media Air Cleaner specifications.


Air Cleaners | History of our Air Filtration Systems | Why AQE Air Cleaners?
Commercial Air Cleaners | Mist Collectors | Soldering Fume Extraction Systems | Welding Fume Extraction
  Hospital  Isolation Rooms/Infection Control | HEPA Air Cleaners | Air Purifiers and Cleaners Site Map | Air Cleaner FAQ's
Articles on Air Quality & Health  | Additional Air Purifier Resources

Contact Air Quality Engineering | Email Air Quality Engineering